DatasheetQ Logo
Electronic component search and free download site. Transistors,MosFET ,Diode,Integrated circuits

3RV1121-4AA10 データシートの表示(PDF) - Siemens AG

部品番号
コンポーネント説明
メーカー
3RV1121-4AA10
Siemens
Siemens AG Siemens
3RV1121-4AA10 Datasheet PDF : 72 Pages
First Prev 11 12 13 14 15 16 17 18 19 20 Next Last
Accessories and ordering data
Surge suppressor (Varistor) for 3TF46-56
1. Mechanical interlocking kit
Mechanical interlock is required when the supply from two
different sources is available. Also the same is required for the
application involving reversing of motor. Here two contactors
are mechanically interlocked with the help of mechanical
interlock kit. This ensures closing of only one contactor at a
time. Thus prevents a short circuit upon load changeover from
one contactor to another.
For Contactor
AC3 Rating
Contactor
9 to 38A
3TF30 to 35
45/63/70A
3TF46/47/47-7
75/85A
3TF48/49
110/140A
3TF50/51
170/205A
3TF52/53
250/300A
3TF54/55
400 A
3TF56
110/170 A
3TF50/52
170/250 A
3TF52/54
MLFB
3TX4 091-1A #
3TX7 466-1YA0
3TX7 486-1YA0
3TX7 506-1YA0
3TX7 526-1YA0
3TX7 546-1YA0
3TX7 566-1YA0
3TX7 526-1YA09
3TX7 546-1YA09
Std. pkg.
(nos.)
10
2
2
2
2
2
2
1
1
#: W/O base plate (not required)
2. Surge suppressor
It is used to reduce the effect of switching overvoltages created
during the opening of inductive circuits. Typically they are
mounted outside the body of the contactor, and are connected
in parallel with the coil terminals. Various techniques for the
suppression of switching overvoltages can be employed. For
example: RC element, Varistor etc.
Coil Voltage
AC
DC
Less than 48V
24 - 70V
48 - 127V
70 - 150V
127 - 240V
150 - 250V
240 - 400V
400 - 600V
Type
3TX7 462-3GY1
3TX7 462-3HY1
3TX7 462-3JY1
3TX7 462-3KY1
3TX7 462-3LY1
Std. pkg.
(nos.)
10
Surge suppressor (RC Element) for 3TF30-3TF35
Coil Voltage
AC
DC
24 - 48V
24 - 70V
48 - 127V
70 - 150V
127 - 240V
150 - 250 V
240 - 400V
400 - 460V
Type
3TX7 402-3RY2
3TX7 402-3SY2
3TX7 402-3TY2
3TX7 402-3UY2
3TX7 402-3VY2
Std. pkg.
(nos.)
10
3. Connector
The 3TS90 connector is used to mount the motor protection
circuit breaker 3VU on the contactor 3TF with screw terminals.
It enables mechanical and electrical connection between
contactor and motor protection circuit breaker.
RC Element:
RC element
The effective increase in the capacitance of
the coil circuit reduces the amplitude and rate
of rise of switch off overvoltage spikes to such
an extend that no rapid restriking occur.
Varistor:
Varistor
Varistor limit the maximum value of the
overvoltage because they become highly
conductive above a threshold value. Until this
threshold value is reached shower discharge
occurs for small duration.
Selection table:
Surge suppressor (Varistor) for 3TF30-3TF35
Coil Voltage
AC
DC
24 - 48 V
24 - 70V
48 - 127V
70 - 150V
127 - 240V
150 - 250V
240 - 400V
400 - 600V
Type
3TX7 402-3GY1
3TX7 402-3HY1
3TX7 402-3JY1
3TX7 402-3KY1
3TX7 402-3LY1
18
Std. pkg.
(nos.)
10
Range:
Size
of
connector
MPCB
MLFB
Current
Rating
Contactor
MLFB
AC3
Current
Rating
I
3VU13 0.16 to 3TF30 / 31 9 / 12 A
20A
II
3VU13 6 to 25A 3TF32 / 33 16 / 22A
MLFB of
Connector
3TS90 01-8K
3TS90 02-8K
Std.
pkg.
(nos.)
1
1
Benefits:
Direct mounting of 3VU MPCB on 3TF contactor eliminates the
need of power wiring and ensures secure connection. In addition,
the assembly time and size of the feeder is reduced which results
in cost saving. The overall assembly also looks contemporary.

Share Link: 