DatasheetQ Logo
Electronic component search and free download site. Transistors,MosFET ,Diode,Integrated circuits

6EP1321-1SH03 データシートの表示(PDF) - Siemens AG

部品番号
コンポーネント説明
メーカー
6EP1321-1SH03
Siemens
Siemens AG Siemens
6EP1321-1SH03 Datasheet PDF : 44 Pages
First Prev 11 12 13 14 15 16 17 18 19 20 Next Last
Applications
5.2 Parallel connection for redundancy
5.2
Parallel connection for redundancy
The parallel switching of several LOGO!Power power supplies for redundancy is required
when the demands for reliability of the supply are particularly high.
If a component in the redundant supply fails, the power supply for the loads must be fully
accommodated by the remaining component. It is therefore important when dimensioning the
system to make sure that n+1 redundant switched power supplies can handle the total power
requirement of the remaining n power supplies.
To prevent loading of the remaining power supplies in the event of a secondary-side error
when one power supply fails, the respective "+" terminals of the power supplies must be
decoupled via diodes.
NOTICE
For a high reliability of the supply, it is recommended that the redundant switched power
supplies are fused separately on the line-side and, if possible, be connected to different
power supply networks.
Figure 5-2 Parallel connection for redundancy
LOGO!Power
20
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619

Share Link: 

datasheetq.com  [ Privacy Policy ]Request Datasheet ] [ Contact Us ]