DatasheetQ Logo
Electronic component search and free download site. Transistors,MosFET ,Diode,Integrated circuits

K8AB-VS データシートの表示(PDF) - OMRON Corporation

部品番号
コンポーネント説明
メーカー
K8AB-VS
Omron
OMRON Corporation Omron
K8AB-VS Datasheet PDF : 10 Pages
1 2 3 4 5 6 7 8 9 10
Nomenclature
Front
Terminal block
(See notes 1 and 2.)
Power indicator
Relay status indicator
Alarm indicator
Voltage knob (SV)
Hysteresis knob (HYS.)
Operating time knob (T)
Terminal block
(See notes 1 and 2.)
K8AB-VS
Indicators
Item
Power indicator
(PWR: Green)
Relay status indicator
(RY: Yellow)
Alarm indicator
(ALM: Red)
Meaning
Lit when power is being supplied.
Lit when relay is operating
Lit when there is an overvoltage or
undervoltage.
The indicator flashes to indicate the error
status after the input has exceeded the
threshold value while the operating time is
being clocked.
Setting Knobs
Item
Usage
Voltage knob (SV)
Used to set the voltage to 10% to 100% of
maximum measuring voltage.
Hysteresis knob (HYS.) Used to set the rest value to 5% to 50% of
the operating value.
Operating time knob (T) Used to set the operating time to 0.1 to 30 s.
Note: 1. Use either a solid wire of 2.5 mm2 maximum or a ferrule with
insulating sleeve for the terminal connection.
The length of the exposed current-carrying part inserted
into the terminal must be 8 mm or less to maintain dielectric
strength after connection.
For 2.5 mm2 or
smaller solid wires
For ferrules with
insulating sleeves
8 mm max.
Recommended ferrules
Phoenix Contact
Al 1,5-8BK (for AWG16)
Al 1-8RD (for AWG18)
Al 0,75-8GY (for AWG18)
2. Tightening torque
Recommended: 0.49 N·m
Maximum: 0.54 N·m
8 mm max.
6

Share Link: 

datasheetq.com  [ Privacy Policy ]Request Datasheet ] [ Contact Us ]