MTL5513 SWITCH/
PROXIMITY DETECTOR
INTERFACE
two-channel, with line fault detection
and phase reversal
The MTL5513 enables two solid-state outputs in the safe area to
be controlled by two switches or proximity detectors located in the
hazardous area. The Ch1/Ch2 output transistors share a common
terminal and can switch +ve or -ve polarity signals. Independent output
phase reversal and line fault detection are enabled via switches for
each output. LFD indication is provided on the top of the module.
Hazardous area
Switch-type sensors
require resistors
if LFD is selected
680W
22kW
680W
22kW
Safe area
To earth
leakage
detector
+6
5
–4
+
3
2
–1
EPS5513-2
7
8
9
Outputs
10
Ch 2
11
12
Ch 1
13
Vs–
14
Vs+
20 to 35V dc
SPECIFICATION
See also common specification
Number of channels
Two
Location of switches
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detectors
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200µA (650Ω) nominal
Line fault detection (LFD) (when selected)
User-selectable for each channel via switches on the side of the
unit. Line faults are indicated by an LED for each channel.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch
Phase reversal
Independent for each channel, user-selectable
Safe-area outputs
Floating solid-state outputs compatible with logic circuits
Operating frequency:
dc to 500Hz
Max. off-state voltage:
± 35V
Max. off-state leakage current:
± 50µA
Max. on-state resistance:
25Ω
Max. on-state current:
± 50mA
Terminal
Function
1
Input –ve (Ch 1)
2
Input +ve (Ch 1)
3
To earth leakage detector*
4
Input –ve (Ch 2)
5
Input +ve (Ch 2)
6
To earth leakage detector*
10
Output (Ch 2)
11
Output (Ch 1/Ch 2)
12
Output (Ch 1)
13
Supply –ve
14
Supply +ve
* Signal plug HAZ1-3 is required for access to this function
LED indicators
Green: power indication
Yellow: two: channel status, on when outputs are on
Red: two: LFD indication, on when line fault detected
Maximum current consumption
27mA at 24V
Power dissipation within unit
0.65W typical at 24V, with 10mA loads
0.78W max. with 50mA loads
Safety description (each channel)
Vo=10.5V Io=14mA Po=37mW Um = 253V rms or dc
The given data is only intended as a product description and should not be re-
garded as a legal warranty of properties or guarantee. In the interest of further
technical developments, we reserve the right to make design changes.
EUROPE (EMEA)
Tel: +44 (0)1582 723633
Fax: +44 (0)1582 422283
AMERICAS
Tel: +1 281 571 8065
Fax: +1 281 571 8069
ASIA PACIFIC
Tel: +65 6 487 7887
Fax: +65 6 487 7997
E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com
Aug 2008

Share Link: 

datasheetq.com  [ Privacy Policy ]Request Datasheet ] [ Contact Us ]