Technical specifications1
fORmAT
Form factor
700 VA: Mini-tower
1000–1500 VA: Mini-tower or
rack/tower 2U
2200–3000 VA: Rack/tower 2U
and rack/tower 3U
ElECTRICAl ChARACTERIsTICs
Topology
Online with automatic bypass and
power factor correction
Input voltage/frequency range
(without batteries)
700–1500 VA: 100/120/140/1602 to 284V,
40–70 Hz
2200–3000 VA: 503–100V to 142V,
40–70 Hz
Output voltage/frequency
120V (adjustable to 100/110/127V),
50/60 Hz, auto-select or frequency
converter mode4
CONNECTIONs
Input
Outputs
Additional outputs with
HotSwap MBP
Additional outputs with FlexPDU
700–1500 VA: 5-15P
2200 VA: NEMA 5-20P
3000 VA: NEMA L5-30P
700–1500 VA : (4) 5-15R tower, (6) 5-15R
RT2U
2200 VA: (6) NEMA 5-20R + (1) NEMA
L5-20R
3000 VA: (6) NEMA 5-20R + (1) NEMA
L5-30R
700–1500 VA: (4) NEMA 5-15R
2200–3000 VA: (5) NEMA 5-15R or
(5) NEMA 5-20R
NEMA L5-20R
2200–3000 VA: (10) NEMA 5-15R or
(10) NEMA 5-20R or (8) NEMA L5-20R
INTERfACEs
Indicators and display
Communication ports
Communications card slots
(3) LEDs + adjustable multilingual
display: display of measurements,
access to control and setup menus
(1) USB port, (1) RS232 serial port and
relay contacts5, (1) mini terminal block
for remote On/Off and emergency stop
(1) slot for NMC Mini-Slot 2006
card, NMC ModBus/JBus or MC
Contacts/Serial
OPERATINg CONdITIONs, sTANdARds ANd APPROvAls
Operating temperature
32°F to 104°F (0°C to 40°C) continuous
Noise level
45 dBA
Performance/Safety/EMC
700–1500 VA: IEC 62 040-3 (VFI-SS-113),
IEC 62 040-1-1, IEC 60 950-1 (RD), FCC
Subpart B, class A
2200–3000 VA: IEC/EN 62 040-3 (VFI-
SS-113), IEC/EN 62 040-1-1, IEC/EN 60
950-1 (RD), IEC/EN 62 040-2 C1, FCC
Subpart B, Class A
Approvals
700–1500 VA: UL, cUL, CE, CB report
2200–3000 VA: CE, TüV, CB Report, UL
and CUL (CSA)
1. Due to continuing product improvement programs, specifications are subject to change without notice
2. Lower limits for <20%, <33%, <66%, >=66% of nominal power (VA); for active output power greater
than 0.7 and 0.8 nominal rating, the lower limit is 180V and 190V respectively
3. Lower limits for reduced load
4. Derated by 15% when used as a frequency converter
5. USB and RS232 serial ports cannot be used simultaneously
EX BATTERY BACKUP TImEs (IN mINUTEs)1
Load
Internal
(VA/Watts) Batteries
+1 EBM
+2 EBMs +3 EBMs +4 EBMs
EX 700
70/49
71
-
-
-
-
140/98
36
-
-
-
-
210/147 25
-
-
-
-
280/196 20
-
-
-
-
350/245 16
-
-
-
-
420/294 12
-
-
-
-
490/343 10
-
-
-
-
560/392 8
-
-
-
-
630/441 6
-
-
-
-
700/490 5
-
-
-
-
EX 1000 / 1000 RT 2U
100/70
75
290
490
790
980
200/140 40
170
290
440
550
300/210 28
125
210
310
390
400/280 21
92
180
240
310
500/350 18
75
150
205
250
600/420 14
60
110
170
220
700/490 11
52
90
145
190
800/560 9
43
78
125
170
900/630 7
40
70
112
155
1000/700 6
35
60
95
135
EX 1500 / 1500 RT 2U
150/105 60
212
360
475
700
300/210 32
110
220
280
380
450/315 21
78
155
210
260
600/420 16
60
115
160
200
750/525 13
47
83
140
180
900/630 10
40
71
110
140
1050/735 8
34
60
90
118
1200/840 7
30
52
76
100
1350/945 6
27
48
70
90
1500/1050 5
24
42
62
80
EX 2200 RT 2U & 3U2
220/154 90
352
587
831
1216
440/308 48
200
340
470
650
660/462 30
130
225
320
450
880/616 22
100
170
260
350
1100/770 16
80
135
215
286
1320/924 13
62
110
180
240
1540/1078 10
50
95
150
200
1760/1232 8
42
80
125
170
1980/1386 7
36
65
110
152
2200/1540 6
30
51
83
134
EX 3000 RT 2U & 3U3
300/210 79
254
454
628
847
600/420 40
130
255
330
445
900/630 25
80
160
230
290
1200/840 18
60
120
180
230
1500/1050 14
48
102
143
187
1800/1260 12
38
82
115
150
2100/1470 9
32
72
95
125
2400/1680 7
27
58
80
100
2700/1890 6
22
50
70
82
3000/2100 5
18
36
52
70
EX 3000 RT 3U XL4
300/210 -
175
375
549
768
600/420 -
90
215
290
405
900/630 -
55
135
205
265
1200/840 -
42
102
162
212
1500/1050 -
34
88
129
173
1800/1260 -
26
70
103
138
2100/1470 -
23
63
86
116
2400/1680 -
20
51
73
93
2700/1890 -
16
44
64
76
3000/2100 -
13
31
47
65
1. Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature,
etc. The EX has a 0.9 power factor, but runtimes are shown here at 0.7 power factor for easy comparison against
competitor's products, which have a 0.7 power factor. 2. Output power rating = 1650W. 3. Standard configura-
tion power rating = 2550W, with EBM = 2100W. 4 Output power rating = 2150W; up to 12 EBMs can be added for
extended runtime of 196-1909 minutes
www.eaton.com/powerquality 1.800.356.5794