High Speed Fuses
General applications
Rated Voltage
The ac voltage rating of Cooper Bussmann® fuses is given in
volts rms. Fuses tested to IEC are tested at 10% above their
rated voltage. British Style BS 88 fuses are tested at 5%
above its rated voltage. UL recognition tests are performed at
the rated voltage.
Rated Current
Rated current is given in amperes rms. Cooper Bussmann
fuses can continuously carry the rated current.
Melting Characteristic
The melting char-
acteristic shows
the virtual melting
time in seconds as
a function of the
prospective current
in amperes rms.
The fuses are spe-
cially constructed
for short-circuit pro-
tection against high
level fault currents.
Loading and opera-
tion of the fuse in
the non-continu-
ous/dashed section
of the melt curve
must be avoided.
The curve can also
be read as the real
melting time as a
function of the
RMS value of the
pre-arc current.
104
6
4
2
103
6
4
2
102
6
4
2
101
6
4
2
100
6
4
2
10–1
6
4
2
10–2
6
4
2
10–3
6
4
2
10–4
101
2
4 6 8 102
2
4 6 8 103
Prospective Current In Amperes RMS
Clearing Integrals
The total clearing I2t at
rated voltage and at
power factor of 15% are
given in the electrical
characteristics. For
other voltages, the
clearing I2t is found by
multiplying by correction
factor, K, given as a
function of applied work-
ing voltage, Eg, (rms).
1.5
K
1.0
0.5
0.4
0.3
0.2
Eg
100 200 300 400 500 600 660
For other power factor
X
values, the total clearing
1.0
integral can be calculat-
ed as a multiple of the
clearing integrals, the
correction factor K and 0.9
the correction factor X.
0.8
Arc Voltage
This curve gives the
peak arc voltage, UL,
which may appear
across the fuse during its
operation as a function
of the applied working
voltage, Eg, (rms) at a
power factor of 15%.
Power Losses
Watts loss at rated cur-
rent is given in the electri-
cal characteristics. The
curve allows the calcula-
tion of the power losses
at load currents lower
than the rated current .
The correction factor, Kp ,
is given as a function of
the RMS load current, Ib ,
in % of the rated current .
Cut-Off Current
0.7
0.1
0.2
0.3
0.4
0.5
COS
1.4
1.2 UL
103
9
8
7
6
5
4
3
Eg
200 300 400 500 600 660
1.0 Kp
0.8
0.6
0.5
0.4
0.3
0.2
0.1
Ib
30 40 50 60 70 80 90 100%
A fuse operation relating to short-circuits only. When a fuse
operates in its current-limiting range, it will clear a short-cir-
cuit in less than 12 cycle. Also, it will limit the instantaneous
peak let-through current to a value substantially less than
that obtainable in the same circuit if that fuse were replaced
with a solid conductor of equal impedance.
105
104
103
A
B
2 10 2
102
103
104
105
106
Prospective Current in Amperes RMS
A asymmetrical current
B symmetrical current
88
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp