2 | C-Series Circuit Breaker - General Specifications
Electrical
Maximum Voltage
AC, 480 WYE/277 VAC, 50/60 Hz
(see Table A.)
UL489: AC,240 VAC. (See Table D),
50/60 Hz, 125 VDC
Current Rating
Standard current coils: 0.100,
0.250, 0.500, 0.750, 1.00, 2.50,
5.00, 7.50, 10.0, 15.0, 25.0, 30.0,
35.0, 40.0, 50.0, 60.0, 70.0, 80.0,
90.0 and 100 amps. Other ratings
available, see Ordering Scheme.
Standard Voltage Coils DC - 6V, 12V; AC - 120V; other
ratings available, see Ordering
Scheme.
Auxiliary Switch Rating SPDT; 10.1 amps-250VAC, DC Aux.
Switch 1.0A, 65 VDC. 0.5A,
80VDC,1/4 HP, 125VAC,VDE & TUV
1.0 125 VAC.
Insulation Resistance Minimum of 100 Megohms at 500
VDC.
Dielectric Strength
UL, CSA: 1960 V 50/60 Hz for one
minute between all electrically
isolated terminals. C-Series Circuit
Breakers comply with the 8mm
spacing and 3750V 50/60 Hz
dielectric requirements from
hazardous voltage to operator
accessible surfaces, between
adjacent poles and from main
circuits to auxiliary circuits per
Publications EN 60950 and
VDE 0805.
Resistance, Impedance Values from Line to Load Terminal -
based on Series Trip Circuit
Breaker. RESISTANCE, IMPEDANCE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
1000
CURRENT TOLERANCE
100
(AMPS)
(%)
10
O
H1
M
S
0.1
0.01
0.001
0.01
0.1
1
10
100
AMPERE RATING
0.10 - 5.0
15
5.1 - 20.0
25
20.1 - 50.0 35
Ir
25x
60 Hz 1/2 Cycle
Inrush Pulse Tolerance
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
Time Delay Curves
22, 24 (100 Amps Max.)
12x
26 (70 Amps Max.)
4.165 8.33
t
16.67
Pulse Tolerance Curves CURRENT
(AMPS)
TOLERANCE
(%)
0.100 - 5.0
15%
60 Hz51.1/2- 2C0y.0cle
25%
Inrush Pu2l0s.1e-T1o0l0erance 35%
Ir
Time DelFayIGCUurvReEs 1
42, 44 & 46
25x
(50 Amps Max.)
Time Delay Curves
22, 24 (100 Amps Max.)
12x
26 (70 Amps Max.)
4.165 8.33
t
16.67
Ir
22x
10x
50 Hz 1/2 Cycle
Inrush Pulse Tolerance
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
Time Delay Curves
22, 24 (100 Amps Max.)
26 (70 Amps Max.)
t
5.0
10.0
20.0
Time in
Milliseconds
Ir
22x
50 Hz 1/2 Cycle
Inrush Pulse Tolerance
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
10x
Time Delay Curves
22, 24 (100 Amps Max.)
26 (70 Amps Max.)
t
*Manufacturer
5r.e0 serv1e0.s0
the
right
to
20.0
cThiamnegine
product
specification
without
prior
notice.
Milliseconds
Mechanical
Endurance
Trip Free
Trip Indication
10,000 ON-OFF operations @ 6 per
minute; with rated current &
voltage.
All C-Series circuit breakers will trip
on overload, even when actuator is
forcibly held in the ON position.
The operating actuator moves
positively to the OFF position when
an overload causes the breaker to
trip. With mid-trip, handle moves to
the mid position on electrical trip of
the circuit breaker. With mid trip
handle with alarm switch, handle
moves to the mid position and the
alarm switch actuates when the
circuit breaker is electrically
tripped.
Physical
Number of Poles
Internal Circuit Config.
Weight
Standard Colors
1-6 poles ≤ 50A; 1-4 poles @ 51-
70A; 1-2 poles 71-100A. UL489
Handle: 1 pole ≤ 100A, 2 pole ≤
50A; Rocker: 1 pole ≤ 100A.
Series (with or without auxiliary
switch, mid trip & mid trip with
alarm switch) Shunt & Relay with
current or voltage trip coils, Dual
Coil, Switch Only (with or without
aux. switch). UL489: Series (with or
without auxiliary switch, mid-trip &
midtrip with alarm switch).
Approx.112 grams/pole ( 3.95 oz).
Housing: Black
Environmental
Designed and tested in accordance with requirements of
specification MIL-PRF-55629 & MIL-STD-202 as follows:
Shock
Withstands 100 Gs, 6ms sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultrashort curves
tested @ 90% of rated current.
Vibration
Withstands 0.060” excursion from
10-55 Hz & 10 Gs 55-500 Hz, @
rated current per Method 204C,
Test Cond. A. Instantaneous &
ultrashort curves tested @ 90% of
rated current.
Moisture Resistance Method 106D, i.e., ten 24-hour
cycles @ +25°C to +65°C,
80-98% RH.
Salt Spray
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Thermal Shock
Method 107D, Condition A (five
cycles @ -55°C to +25°C to +85°C
to +25°C).
Operating Temperature -40°C to +85°C